Harmonic Filters and Transformers / Harmonic Filters / 5,67%

Three phase harmonic filters Construction and Materials
  • Three phase harmonic filters.
  • Avoid resonance between inductive impedance and three phase capacitors for power factor correction.
  • Detuning with MA/C/CE TER RCT and DWCAP RCT, with resonance frequency 134, 189 or 210 Hz.
  • Low losses magnetic plates.
  • Copper and aluminium conductor reactor insulation thermal class F (155ºC) with permanent regime.
  • Thermal protection relay.
  • Specially designed to increasing ventilation, and improving thermal dissipation.
  • Thermal class of electrical insulating material 180ºC.
Upon request Standards
RTR’s technical team offers the possibility of manufacturing equipment according to customer application need, different power, voltage, frequency…
  • UNE-EN 60076-6.
  • IEC 60076-6.
Code Pow. Volt. Nominal Freq. Resonance Freq. Detuning Fac. Capacitance Current Inductance
KVAr V Hz Hz % µF A mH
RTF040001002105 10 400 50 210 5,67 187,66 14,43 3,06
RTF040001252105 12,5 400 50 210 5,67 234,58 18,04 2,45
RTF040001502105 15 400 50 210 5,67 281,50 21,65 2,04
RTF040002002105 20 400 50 210 5,67 375,33 28,87 1,53
RTF040002502105 25 400 50 210 5,67 469,16 36,08 1,22
RTF040005002105 50 400 50 210 5,67 938,32 72,17 0,61
RTF040008002105 80 400 50 210 5,67 1501,31 115,47 0,38
RTF040010002105 100 400 50 210 5,67 1876,64 144,34 0,31
Technical Characteristics
Tolerance “L” 5%
Frequency networks 50/60 Hz
Linearity Inductance 1,8 x In
Detuning factor 5,67%, 7%, 14%
Proof strees 4 kV
Thermal Protection 90º C, 120º C, 140º C
Permissible Overload 1,17 x In
Protection Degree IP-00