• Three-phase detuned reactor for harmonic filtering.
• They avoid resonance between the inductive impedance (line, power transformer) and the three-phase capacitors used for power factor correction.
• Tuned with capacitors MA/C/CE TER RCT or DWCAP RCT, at resonance frequencies of 210, 189 Hz or 134 Hz (252, 227 and 160 Hz if the nominal
frequency is 60 Hz).
The technical department of RTR Energy offers the possibility of manufacturing equipment according to the needs of customer application, defining power, voltage, frequency…
Dimensions and weight, consult.
• Very low loss magnetic plate.
• Aluminum conductor.
• Thermal protection.
• Specially designed windings to increase ventilation and improve heat
dissipation.
• Dry type vacuum varnished for ensure quiet operation and moisture resistance.
• UNE-EN 60076-6
• IEC 60076-6
Technical characteristics
Nominal Frequency 50Hz (60Hz on request) Linearity inductance • 7% Linearity= 1,9 x In
• 14% Linearity= 1,7 x In
Thermal Protection 132° C
Detuning Factor 7%, 14% (Other frequencies
on demand
)
Insulation Voltage 3kV Thermal insulation H (180ºC)
Tolerance (Inductance) ±5% Maximum overload 1,1 x In Degree of Protection IP-00