Utility and characteristics |
Upon Request | Materials and construction |
Certificates |
---|---|---|---|
• Three-phase detuned reactor for harmonic filtering. • They avoid resonance between the inductive impedance (line, power transformer) and the three-phase capacitors used for power factor correction. • Tuned with capacitors MA/C/CE TER RCT or DWCAP RCT, at resonance frequencies of 210, 189 Hz or 134 Hz (252, 227 and 160 Hz if the nominal frequency is 60 Hz). |
The technical department of RTR Energy offers the possibility of manufacturing equipment according to the needs of customer application, defining power, voltage, frequency… Dimensions and weight, consult. |
• Very low loss magnetic plate. • Aluminum conductor. • Thermal protection. • Specially designed windings to increase ventilation and improve heat dissipation. • Dry type vacuum varnished for ensure quiet operation and moisture resistance. |
• UNE-EN 60076-6 • IEC 60076-6 |
Technical characteristics | |||||
---|---|---|---|---|---|
Nominal Frequency | 50Hz (60Hz on request) | Linearity inductance | • 7% Linearity= 1,9 x In • 14% Linearity= 1,7 x In |
Thermal Protection | 132° C |
Detuning Factor | 7%, 14% (Other frequencies on demand) |
Insulation Voltage | 3kV | Thermal insulation | H (180ºC) |
Tolerance (Inductance) | ±5% | Maximum overload | 1,1 x In | Degree of Protection | IP-00 |