Utility and characteristics |
Upon Request | Composition and materials |
Certificates |
---|---|---|---|
• Protected three-phase capacitor. • Designed for reactive power factor correction. • Indoor mounting in ventilated environment. • Equipment internal temperature ≤55˚ C. •IP20. |
The RTR comercial-tecnician team offers the possibility of designing equipment to suit the customer, defining power, voltage and auxiliary equipment. | • DWCAP or MA/C/CE Capacitors. • Automatic relay for one or two steps, which connects or disconnects steps according to consumption of reactive energy to compensate. • Contactors adapted to breaking mounted capacitive currents with discharge resistors. • Automatic MCB Circuit breaker. • Top left cable entry. • Galvanized sheet metal cabinet and RAL 1013 cover. |
• IEC 60831-1/2. • UNE-EN 60831-1/2. |
Technical Characteristics | |||||
---|---|---|---|---|---|
Capacitance tolerance | -5% +10% | Max. THD/U | 2% | Peak current | Until 200 x In |
Frequency | 50Hz (60Hz under demand) | Max. THD/I | 25% | Protection degree | IP-20 |
Temperature range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Connections | Delta | Useful life | 130.000h |
Total losses | ≤0.45 W/KVAr (without resistance) | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10 x Un (up 8h/day) 1.15 x Un (up 30min/day) 1.20 x Un (up 5 min/day) 1.30 x Un (up 1 min/day) |
Test voltage between terminals and box |
5kV AC para 1min | Installation position | Universal |
Overcurrent | 1.50xIn (including effects of overvoltage and capacity tolerances) |