Utility and characteristics |
Triple security | Composition and materials |
Normative and certificates |
---|---|---|---|
• Three-phase capacitor DUAL WINDOWS. • Triangle coupling. • Built-in discharge resistance. • Power factor correction. • Oversized to withstand surges. • Dry type. • Connector. • Indoor use. |
• Disconnection system above Pressure. • Protection by internal fuses. • DWCAP system (PATENTED) by internal displacement of the coils. |
• Metallized polypropylene film low-loss self-healing, high density, high temperature and higher dielectric strength Volts/μ. • Self-extinguishing polyurethane resin V0, elaborated under regulations UL 94 by RTR Energy and with certification 20141031-E470994. • Aluminum pot M12x16. |
• IEC 60831-1/2:2014 • UNE-EN 60831-1/2:2014 • UL 94. 20141031-E470994 |
Technical Characteristics | |||||
---|---|---|---|---|---|
Tolerance Power |
-5% +10% | Max. Harmonic distortion | 3% | Peak current | Until 350 x In |
Frecuency | 50Hz (60Hz under demand) | Distortion arm.max. in intensity | 30% | Protection degree | IP-20 |
Climatic range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Coupling | Triangle | Useful life | 150.000h |
Total losses | ≤0.4 W/KVAr (without resistance) | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.15 x Un (up 30min/day) | Test voltage between terminals and box |
5kV AC para 1min | Installation position | Universal |
Overcurrent | 1.80xIn (including effects of overvoltage and capacity tolerances) |