Utility and
characteristics
Triple security Constructions and
Materials
Certifiactes
• Three-phase capacitor.
• DWCAP in metallic box.
• Delta connection.
• Built-in discharge resistance.
• Reactive power factor correction.
• Reinforced design to support overvoltage.
• Dry type.
• Connector type terminal.
• Indoor mounting.
• Overpressure disconnection system.
• Protection by internal fuses.
• DWCAP system (PATENTED) Internal windings displacement.
• Metallized polypropylene film low loss self-healing, high density, high temperature and higher dielectric strength Volts / μ.
• Self-extinguishing polyurethane resin V0, prepared under UL 94 regulations by RTR Energía and with certification
20141031-E470994.
• Metal container with terminal cover and fixing fins.
• RAL 6034.
• IEC 60831-1/2:2014
• UNE-EN 60831-1/2:2014
• UL 94. 20141031-E470994
Technical Characteristics
Capacitance tolerance -5% +10% Max. THD/U 3% Peak current Until 350xIn
Frequency 50Hz (60Hz under demand) Max. THD/I 30% Protection degree IP-20
Temperature range -25ºC +55ºC (/D) Discharge resistance Incorporated Humidity Max. 95%
Dielectric losses ≤0.2 W/KVAr Connection Delta Useful life 150.000h
Total losses ≤0.40 W/KVAr * Test voltage between terminals 2.15 xUn 10s Altitude Máx. 4000 m.s.n.m.
Overvoltage 1.15xUn (until 30 min/day) Test voltage between terminals
and box
5kV AC for 1min Installation position Universal
Overcurrent 1.80xIn (including effects of
overvoltage and capacity
tolerances
)