Utility and characteristics | Constructions and Materials | Normatives and certificates |
---|---|---|
• Three-phase capacitor. • DWCAP in metallic box. • Triangle coupling. • Built-in discharge resistance. • Power factor correction. • Oversized to withstand surges. • Special design for series coupling with passive filters tuned to the resonance frequency of 189 Hz. • Power factor correction. • Dry type. • Connector. • Indoor use. |
• Prismatic triphasic condenser. • Power factor correction. • Dry type. • Connection of single-phase elements by means of a threaded stud. • Built-in discharge resistance. • Indoor use. |
• IEC 60831-1/2: 2014 • UNE-EN 60831-1/2: 2014. • UL 94. 20141031-E470994. |
Technical Characteristics | |||||
---|---|---|---|---|---|
Tolerance Power |
-5% +10% | Max. Harmonic distortion | 2% | Peak current | Until 200xIn |
Frequency | 50Hz (60Hz under demand) | Distortion arm.max. in intensity | 25% | Protection degree | IP-20 |
Climatic range | -25ºC +55ºC (/D) | Discharge resistance | Incorporada | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Coupling | Triángulo | Useful life | 100.000h |
Total losses | ≤0.50 W/KVAr * | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10xUn (hasta 8h/day) 1.15xUn (hasta 30min/day) 1.20xUn (hasta 5 min/day) 1.30xUn (hasta 1 min/day) |
Test voltage between terminals and box |
3kV AC for 1min | Installation position | Universal |
Overcurrent | 1.50xIn (including effects of overvoltage and capacity tolerances) |
* Without resistence