Utility and characteristics |
Triple security | Constructions and Materials |
Normatives and certificates |
---|---|---|---|
DOUBLE WINDING three-phase capacitor • Coupling in a triangle • Integrated discharge resistance. • Power factor adjustment. • Dry kind. • Interconnectors. • For use inside |
• System disconnection above pressure. • Internal fuses provide protection. • DWCAP system (PATENTED) based on coil internal displacement |
• Self-healing metallized polypropylene film with low losses, high density, high temperature, and increased dielectric resistance Volts / • RTR EnergIa’s self-extinguishing polyurethane resin V0, developed in accordance with UL 94 requirements and certified 20141031-E470994. • M12x16 aluminum pot |
• IEC 60831-1/2:2014 • UNE-EN 60831-1/2:2014 • UL 94. 20141031-E470994 |
Technical Characteristics | |||||
---|---|---|---|---|---|
Tolerance Power | -5% +10% | Max. Harmonic distortion during tension | 2% | Peak current | Until 250xIn |
Frequency | 50Hz (60Hz under demand) | Max. Harmonic distortion during intensity | 25% | Protection degree | IP-20 |
Climatic range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Coupling | Triangle | Useful life | 130.000h |
Total losses | ≤0.40 W/KVAr (Without resistance) | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10xUn (until 8h/day) 1.15xUn (until 30min/day) 1.20xUn (until 5 min/day) 1.30xUn (until 1 min/day) |
Test voltage between terminals box |
5kV AC para 1min | Installation position | Universal |
Overintensity | 1.60xIn (This includes surge impacts as well as capacity tolerances) |