Utility and characteristics |
Doble safety | Constructions and Materials |
Certificates |
---|---|---|---|
• Three-phase capacitor. • Delta connection. • Built-in discharge resistance. • Reactive power factor correction. • Dry type. • Connector type terminal. • Indoor mounting. • Reinforced design to support overvoltage |
• Overpressure disconnection system. • Protection by internal fuses. |
• Metallized polypropylene film low-loss self-healing, high density, high temperature and higher dielectric strength Volts / μ. • Self-extinguishing polyurethane resin V0, prepared under UL 94 regulations by RTR Energía and with certification 20141031-E470994. • M12x16 aluminium case. |
• IEC 60831-1/2:2014 • UNE-EN 60831-1/2:2014 • UL 94. 20141031-E470994 |
Technical Characteristics | |||||
---|---|---|---|---|---|
Capacitance tolerance | -5% +10% | Max. THD/U | 3% | Peak current | Hasta 350xIn |
Frequency | 50Hz (60Hz under demand) | Max. THD/I | 30% | Protection degree | IP-20 |
Temperature range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Connection | Delta | Useful life | 150.000h |
Total losses | ≤0.40 W/KVAr (without resistance) | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10xUn (up 8h/day) 1.15xUn (up 30min/day) 1.20xUn (up 5 min/day) 1.30xUn (up 1 min/day) |
Test voltage between terminals and box |
115kV AC for 1min | Installation position | Universal |
Overcurrent | 1.60xIn (including effects of overvoltage and capacity tolerances) |