Utility and characteristics |
Triple security | Constructions and Materials |
Standards and certificates |
---|---|---|---|
• Three-phase capacitor DUAL WINDING. • Delta connection. • Built-in discharge resistance. • Reactive power factor correction. • Dry type. • Connector type terminal. • Indoor mounting. |
• Overpressure disconnection system. • Protection by internal fuses. • DWCAP system (PATENTED) Internal windings displacement. |
• Self-healing metallized polypropylene film with low losses, high density, high temperature and higher dielectric resistance Volts / μ. • Self-extinguishing polyurethane resin V0, prepared under UL 94 regulations by RTR Energía and with certification 20141031-E470994. •M12x16 aluminium case. |
• IEC 60831-1/2:2014 • UNE-EN 60831-1/2:2014 • UL 94. 20141031-E470994 |
Technical Characteristics | |||||
---|---|---|---|---|---|
Capacitance tolerance | -5% +10% | Max. Harmonic distortion | 4% | Peak current | Until 350 x In |
Frequency | 50Hz (60Hz under demand) | Max. Harmonic distortion intensity | 60% | Protection degree | IP-20 |
Temperature range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Connection | Delta | Useful life | 200.000h |
Total losses | ≤0.40 W/KVAr (Without resistance) | Test voltage between terminals | 2.15 x Un 10s | Altitude | 4000 m.s.n.m. |
Overvoltage | 1.10xUn (8h/day) 1.15xUn (30min/day) 1.20xUn (5min/day) 1.30xUn (1min/day) |
Test voltage between terminals and box |
5kV AC for 1 min | Installation position | Universal |
Overcurrent | 2,05xIn |