Utility and characteristics | Composition | Under order | Normative and certificates |
---|---|---|---|
• Protected three-phase capacitor. • Equipment designed for the compensation of Reactive Energy in installations that do not require automatic regulation. • Indoor use and ventilated environment. • Equipment internal temperature ≤55˚C |
• DWCAP capacitors, MA/C/CE TER or MA/C/CE. • Contactors adapted to breaking mounted capacitive currents with discharge resistors. • General switch protection automatic. • Connection from the top left. • Galvanized sheet metal cabinet and RAL 1013 cover. |
The RTR technical-commercial team Energy offers the possibility of designing equipment to suit the consumer, defining power, voltage, auxiliary equipment… | • IEC 60831-1/2. • UNE-EN 60831-1/2. |
Technical Characteristics | |||||
---|---|---|---|---|---|
Tolerance Power |
-5% +10% | Max. Harmonic distortion | According to tuning frequency filter |
Peak current | Hasta 250xIn |
Frecuency | 50Hz (60Hz under demand) | Discharge resistance | Incorporated | Protection degree | IP-20 |
Climatic range | -25ºC +55ºC (/D) | Coupling | Triangle | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Test voltage between terminals | 2.15 xUn 10s | Useful life | 130.000h |
Total losses | ≤0.45 W/KVAr * | Test voltage between terminals and box |
5kV AC para 1min | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10 x Un (up 8h/day) 1.15 x Un (up 30min/day) 1.20 x Un (up 5 min/day) 1.30 x Un (up 1 min/day) |
||||
Overcurrent | 1.60xIn (including effects of overvoltage and capacity tolerances) |