Utility and characteristics |
Security | Constructions and Materials |
Certificates | Upon Request |
---|---|---|---|---|
• Fixed three phase capacitor • DWCAP in metallic box. • Delta connection. • Built-in discharge resistor. • Reactive power factor correction. • Dry type. • Automatic switch or fuses. • Indoor mounting. |
• Overpressure disconnection system. • Protection by internal fuses. • DWCAP system (PATENTED) due to internal windings displacement. |
• Metallized polypropylene film low-loss self-healing, high density, high temperature and higher dielectric strength Volts/μ. • Self-extinguishing polyurethane resin V0, elaborated under regulations UL 94 by RTR Energy and certified 20141031-E470994. • Metal container with cover terminals and fixing brackets. • RAL 6034. |
• IEC 60831-1/2. • UNE-EN 60831-1/2. |
The RTR technical-commercial team Energy offers the possibility of designing equipment to suit the consumer, defining power, voltage, auxiliary equipment… |
Technical Characteristics | |||||
---|---|---|---|---|---|
Capacitance tolerance | -5% +10% | Max. THD/U | 2% | Peak current | Hasta 250xIn |
Frecuency | 50Hz (60Hz under demand) | Max. THD/I | 25% | Protection degree | IP-20 |
Temperature range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Connections | Delta | Useful life | 130.000h |
Total losses | ≤0.45 W/KVAr * | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10 x Un (until 8h/day) 1.15 x Un (until 30min/day) 1.20 x Un (until 5 min/day) 1.30 x Un (until 1 min/day) |
Test voltage between terminals and box |
5kV AC for 1min | Installation position | Universal |
Overcurrent | 1.60xIn (including effects of overvoltage and capacity tolerances) |