Utility and characteristics |
Composition | Upon Request | Certificates |
---|---|---|---|
• Protected three-phase capacitor. • Equipment designed for the compensation of Reactive Energy in installations that do not require automatic regulation. • Outdoor use. • Protected with automatic switch. |
• Polyester cabinet. • MA/C/CE TER, MA/C/CE and DWCAP. • Automatic switch. |
The RTR technical-commercial team Energy offers the possibility of designing equipment to suit the consumer, defining power, voltage, auxiliary equipment… |
• IEC 60831-1/2. • UNE-EN 60831-1/2. |
Technical Characteristics | |||||
---|---|---|---|---|---|
Capacitance tolerance | -5% +10% | Max. THD/U | 2% | Peak current | Until 200xIn |
Frequency | 50Hz (60Hz under demand) | Max. THD/I | 25% | Protection degree | IP-65 |
Temperature range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Connections | Delta | Useful life | 130.000h |
Total losses | ≤0.45 W/KVAr (Sin resistencia) | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10 x Un (up 8h/day) 1.15 x Un (up 30min/day) 1.20 x Un (up 5 min/day) 1.30 x Un (up 1 min/day) |
Test voltage between terminals and box |
5kV AC for 1min | Installation position | Universal |
Overcurrent | 1.60xIn (including effects of overvoltage and capacity tolerances) |