General description |
Under order | Composition and materials |
|
---|---|---|---|
• Capacitor Banks designed for reactive power factor correction. • Use in industrial instalaciones with the presence of harmonic distortions over 3% – THD/U and 30% – THD/I. • Indoor use and ventilated environment. • Equipment internal temperature ≤ 55˚ C. •IP21 (others avaliable). |
RTR Energía’s technical-commercial team offers the possibility of designing batteries to suit the consumer, defining power, frequency, auxiliary equipment… |
• MA/C/CE/TER RCT or DWCAP RCT capacitors. • Detuned passive filtering reactors conected with capacitors and tuned to frequency 189Hz (other frequencies avaliable). • Contactors adapted to breaking capacitive currents mounted with fast discharge resistors. • Step protection with high breaking capacity fuses. • General load breaking switch or molded case. • Maneuver transformer. • Electronic regulator with microprocessor. • Connection in the upper part of the left side. • Galvanized sheet metal cabinet with RAL 1013 cover. • Accessories: extractors, fans, thermostats, intensity transformers…. |
ARMAdminRTR2024-09-27T13:43:44+00:00