Utility and characteristics |
Triple security | Constructions and Materials |
Normatives and certificates |
---|---|---|---|
• Three-phase capacitor. • DWCAP in metallic box. • Triangle coupling. • Built-in discharge resistance. • Power factor correction. • Dry type. • Connector. • Indoor use. |
• Overpressure disconnection system. • Protection by internal fuses. • DWCAP system (PATENTED) by internal displacement of the coils. |
• Self-healing metallized polypropylene film with low losses, high density, high temperature and higher dielectric resistance Volts / μ. • Self-extinguishing polyurethane resin V0, prepared under UL 94 regulations by RTR Energía and with certification 20141031-E470994. • Metal container with terminal cover cover and fixing fins. • RAL 6034. |
• IEC 60831-1/2:2014 • UNE-EN 60831-1/2:2014 • UL 94. 20141031-E470994 |
Technical Characteristics | |||||
---|---|---|---|---|---|
Tolerance Power |
-5% +10% | Max. Harmonic distortion | 2% | Peak current | Until 250xIn |
Frecuency | 50Hz (60Hz under demand) | Max. Harmonic distortion intensity |
25% | Protection degree | IP-20 |
Climatic range | -25ºC +55ºC (/D) | Discharge resistance | Incorporated | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Coupling | Triángle | Useful life | 150.000h |
Total losses | ≤0.40 W/KVAr (Without resistencia) | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Overvoltage | 1.10xUn (hasta 8h/day) 1.15xUn (hasta 30min/day) 1.20xUn (hasta 5 min/day) 1.30xUn (hasta 1 min/day) |
Test voltage between terminals and box | 5kV AC for 1min | Installation position | Universal |
Overcurrent | 1.60xIn (including effects of overvoltage and capacity tolerances) |