Utility and characteristics | Composition | Under order | Normative and certificates |
---|---|---|---|
• Three-phase capacitor and reactance protected harmonic filtering. • Equipment designed for compensation of reactive energy in installations that do not require automatic regulation and in the presence of harmonics. • Indoor use and ventilated environment. |
• Condenser MA/C/CE TER RCT or DWCAP RCT. • Three-phase surge rejection reactance harmonics. • Galvanized sheet metal cabinet. RAL 1013 cover. • Connection at the top left. • Automatic switch. • Pilot. |
The RTR technical-commercial team Energy offers the possibility of designing equipment to suit the consumer, defining power, voltage, auxiliary equipment… | • IEC 60831-1/2. • EN 60831-1/2. |
Technical Characteristics | |||||
---|---|---|---|---|---|
Tolerance Power |
-5% +10% | Max. Harmonic distortion | According to tuning frequency filter |
Peak current | Hasta 350xIn |
Frecuency | 50Hz (60Hz under demand) | Discharge resistance | Incorporated | Protection degree | IP-20 |
Climatic range | -25ºC +55ºC (/D) | Coupling | Triángle | Humidity | Max. 95% |
Dielectric losses | ≤0.2 W/KVAr | Test voltage between terminals | 2.15 xUn 10s | Altitude | Máx. 4000 m.s.n.m. |
Total losses | ≤0.45 W/KVAr (without resistance) | Test voltage between terminals and box | 5kV AC para 1min | ||
Overvoltage | 1.10 x Un (up 8h/day) 1.15 x Un (up 30min/day) 1.20 x Un (up 5 min/day) 1.30 x Un (up 1 min/day) |
||||
Overcurrent | 1.80xIn (including effects of overvoltage and capacity tolerances) |