Utility and characteristics Constructions and Materials Certificates
• Prismatic three-phase capacitor.
• Reactive power factor correction.
• Reinforced design to support overvoltages.
• Dry type.
• Connection of single-phase elements by means of a
threaded stud.
• Built-in discharge resistance.
• Indoor mounting.
• Self-healing metallized polypropylene film with low losses, high density, high temperature and greater dielectric resistance Volts/μ.
• Self-extinguishing polyurethane resin V, prepared
under UL 94 regulations by RTR Energía and with
certification 20141031-E470994.
• Metal container with terminal cover and fixing brackets.
• RAL 6034.
• IEC 60831-1/2: 2014
• UNE-EN 60831-1/2: 2014.
• UL 94. 20141031-E470994.
Technical Characteristics
Capacitance tolerance -5% +10% Max. THD/U 3% Peak current Hasta 2o0xIn
Frequency 50Hz (60Hz under demand) Max. THD/I 30% Protection degree IP-20
Climatic range -25ºC +55ºC (/D) Discharge resistance Incorporated Humidity Max. 95%
Dielectric losses ≤0.2 W/KVAr Connections Delta Useful life 120.000h
Total losses ≤0.50 W/KVAr (without resistance) Test voltage between terminals 2.15 xUn 10s Altitude Máx. 4000 m.s.n.m.
Overvoltage 1.15xUn (until 30 min/day)  Test voltage between terminals
and box
3kV AC para 1min Installation position Universal
Overcurrent 1.50xIn (including effects of
overvoltage and capacity
tolerances
)