Utility and
characteristics
Triple safety Constructions and
Materials
Certificates
• DUAL WINDING three-phase
capacitor.
• Delta connection.
• Built-in discharge resistance.
• Reactive power factor correction.
• Special design for conection with 210, 189, 134Hz detuned reactors.
• Dry type.
• Connector type terminal.
• Indoor mounting.
• Overpressure disconnection system.
• Protection by internal fuses.
• DWCAP system (PATENTED) internal windings displacement
• Self-healing metallized polypropylene film with low losses, high density, high temperature and higher dielectric resistance Volts / μ.
• RTR Energia’s self-extinguishing polyurethane resin
V0, prepared under UL 94 regulations by RTR Energía and with certification
20141031-E470994.
• M12x16 aluminium case.
• IEC 60831-1/2:2014
• UNE-EN 60831-1/2:2014
• UL 94. 20141031-E470994
*Certified product up to 525V and up to
35kVAr
Technical Characteristics
 
Capacitance tolerance -5% +10% Overcurrent 1.80xIn (This includes surge impacts as well as capacity tolerances) Peak current Until 350xIn
Frequency 50Hz (60Hz under demand) Discharge resistance Incorporated Protection degree IP-20
Temperature range -25ºC +55ºC (/D) Connection Delta Humidity Max. 95%
Dielectric losses ≤0.2 W/KVAr Test voltage between terminals 2.15 xUn 10s Installation position Universal
Total losses ≤0.40 W/KVAr  (Without resistance) Test voltage between terminals
box
5kV AC para 1min Altitude Máx. 4000 m.s.n.m.
Overvoltage 1.15xUn (until 30min/day)